|
|
|
|
|
| 005 | ACU FAULTS See example overlay |
This message is caused by a fault in one of the elevation or azimuth motors, or by a circuit breaker fault. |
|
| 006 | OUT-OF-SERVICE ANTENNA NOT AT ZENITH See example overlay |
An out-of-service antenna is reporting that it is not in the stowed position. This can be caused by maintenance procedures or something severe like loss of control of the antenna. |
|
| 010 | WARM DEWAR (VLA dewar only!) See example overlay |
A dewar could be warm because of maintenance work, or because of a failure (such as a helium leak or refrigerator failure) |
|
| 020 | VERTEX ROOM TEMPERATURE OUT OF RANGE See example overlay |
The vertex room temperature as monitored in the B-rack is either <17 or >23 degrees C. This condition will occur if air flow is lost or if the HVAC system has malfunctioned. |
|
|
|
|
|
|
| 050 | SOURCE CHANGE IN PROGRESS | The observing schedule has specified a source change. | None. |
| 051 | SUBREFLECTOR NOT IN POSITION See example overlay |
Position in Focus/Rotation out by > 10 counts for rotation or > 200 counts for focus. |
|
| 052 | ANTENNA OFF SOURCE | This could be cause by the antenna going through a 360 degree "unwrap", or a 180 degree "over the top" adjustment in azimuth. | None. |
| 053 | L6 OUT OF LOCK See example overlay |
One of the L6s is out of lock. |
|
| 054 | L8 OUT OF LOCK See example overlay |
L8 is out of synchronization. The L8 modules at the antennas are synchronized with the L8 module in the master LO rack. This message applies only to L8 modules at the antennas. |
|
| 055 | BE FILTERS SET WRONG See example overlay |
Backend filters in the T4 are not selected properly. |
|
| 056 | BACKEND TP OUT OF RANGE See example overlay |
Total power as monitored in the T5 is out of range. The acceptable range of total power is 4 - 9 volts. |
|
| 057 | FLAGGED BAD IN IF FILE | Operator | None. |
| 058 | TSYS FLUCTUATIONS See example overlay |
The synchronous detector voltage is varying rapidly. May indicate RFI. |
|
| 059 | FIRST LO OUT OF LOCK See example overlay |
The first LO is out of lock for an observing band that is currently being used. |
|
|
|
|
|
|
| 100 | L6 IN MANUAL See example overlay |
The L6 in the antenna was left in manual. |
|
| 101 | ACU IN MANUAL See example overlay |
ACU computer/local switch has been left in manual position. |
|
| 103 | FRONT END IN MANUAL See example overlay |
The F5 module has been left switched to "Local" and cannot be controlled remotely. Affects all bands. |
|
| 110 | ANTENNA ID - DCS NUMBER CONFUSION See example overlay |
Reported Antenna ID does not match assigned ID to DCS in computer file. |
|
|
|
|
|
|
| 200 | FAN FAULT See example overlay |
The PED room temperature is too high and/or the AC fan is inoperative (no air flow). |
|
| 201 | EMERGENCY STOP See example overlay |
E-Stop switch set. |
|
| 202 | FIRE DETECTION MALFUNCTION | Indicates problem with antenna fire alarm system. |
|
| 203 | FIELD FAULT See example overlay |
Indicates a field winding problem with one of the Servo drive motors. |
|
| 204 | CIRCUIT BREAKER FAULT See example overlay |
|
|
| 205 | DRIVE CABINET OVER TEMPERATURE | The Servo cabinet has reached its overtemp limit. |
|
| 206 | INPUT BREAKER TRIPPED |
|
|
| 207 | MOTOR OVER TEMPERATURE |
One or more Servo drive motors has reached it's overtemp limit & shut down. |
|
| 208 | AZ LIMIT CW See example overlay |
Antenna has reached the physical CW limit of the cable wrap travel region. |
|
| 209 | AZ LIMIT CCW See example overlay |
Antenna has reached the physical CCW limit of the cable wrap travel region. |
|
| 210 | AZ MOTOR FAULT See example overlay |
Any one of the following conditions can generate
an AZ motor fault:
|
|
| 211 | NOT DIGITAL POSITION MODE See example overlay |
ACU has dropped out of pointing mode. |
|
| 212 | EL LIMIT UP See example overlay |
Antenna has reached the physical limit of Elevation UP motion. |
|
| 213 | EL LIMIT DOWN See example overlay |
Antenna has reached the physical limit of Elevation DOWN motion. |
|
| 214 | EL MOTOR FAULT See example overlay |
Any one of the conditions listed under fault #210
can
cause an EL motor fault. |
|
| 215 | POSSIBLE AZIMUTH OSCILLATION See example overlay |
Possible oscillation in AZ axis. |
|
| 216 | POSSIBLE ELEVATION OSCILLATION See example overlay |
Possible oscillation in EL axis. |
|
|
|
|
|
|
| 220 | EXCESSIVE SUB-REFLECTOR ERROR See example overlay |
Change in focus > 4 counts**
Change in focus > 200 counts*** Change in rotation > 4 counts** Change in rotation > 10 counts*** A two star message indicates that data is not greatly affected. A three star message indicates that the data is bad. |
|
| 223 | GROUND NOT ZERO VOLTS See example overlay |
Ground is not at zero volts. The acceptable range is -.045 V to .045 V. |
|
| 224 | F/R ROT FAULT See example overlay |
FRM will not move in Rotation axis. |
|
| 225 | F/R FOCUS FAULT See example overlay |
FRM will not move in Focus axis. |
|
| 226 | F/R SYSTEM FAULT See example overlay |
System faults indicate a problem with the FRM system, such as both limits being set at the same time or a cable that is not plugged in. |
|
|
|
|
|
|
| 300 | L5 GROUND > 0.01V See example overlay |
This message is generated when there is a loose ground connection or a problem in the data set. | Do nothing. The LO/IF group routinely monitors this, and will correct the problem. |
| 301 | L1-J4 5 MHZ REF OUTPUT LOW, <1.5 V See example overlay |
5 MHZ output power on J4 is low. If this power is too low then there will be many more problems. |
|
| 302 | L1-J3 5 MHZ REF OUTPUT LOW, <1.5 V See example overlay |
5 MHZ output power on J3 is low. If this power is too low then there will be many more problems. |
|
| 303 | L1 10 MHZ OUTPUT LOW, <1.5 VSee example overlay | 10 MHZ output power is low. If this power is too low then there will be many more problems. |
|
| 305 | L1 50 MHZ OUTPUT LOW,<1.5 V See example overlay |
50 MHZ output power is low. If this power is too low then there will be many more problems. |
|
| 306 | L2 VCO TUNING > 5V See example overlay |
The VCO control voltage in the L2 is > 5 volts. This means that the tuning voltage in the oscillator has drifted and needs to be adjusted. |
|
| 310 | L2 COMB OUTPUT LOW, < 2.0 V See example overlay |
The output power of the comb generator in the L2 is low. If this power is too low then the L6s will not lock and the front end will also have problems. |
|
| 311 | L3 1200 MHZ VCO TUNING --- SATURATEDSee example overlay | The tuning voltage of the 1200 MHZ VCO in the L3 is at +/- 10 volts. The VCO may be out lock or be very close to it. It is also possible that the VCO is ok, but that there is a monitor problem. |
|
| 313 | L3 1200 MHZ VCO TUNING NOT -5 V TO +8 VSee example overlay | The tuning voltage of the 1200 MHZ VCO in the L3 has drifted out of range. If the L3 1200 MHZ is still locked, the antenna can still be used. |
|
| 314 | L3 1800 MHZ VCO TUNING --- SATURATEDSee example overlay | The tuning voltage of the 1800 MHZ VCO in the L3 is at +/- 10 volts. The VCO may be out lock or be very close to it. It is also possible that the VCO is ok, but that there is a monitor problem. |
|
| 315 | L3 1800 MHZ VCO TUNING NOT -5 V TO +8 VSee example overlay | The tuning voltage of the 1800 MHZ VCO in the L3 has drifted out of range. If the L3 1800 MHZ is still locked, the antenna can still be used. |
|
| 316 | L4 1200 MHZ RECEIVED LEVEL LOW, < 0.5 VSee example overlay | The 1200 MHZ receive level in the L4 at the antenna is low and needs adjusting. There is a danger of the L8 losing sync at this point. |
|
| 317 | L4 1800 MHZ RECEIVED LEVEL LOW, < 0.5 VSee example overlay | The 1800 receive level in the L4 at the antenna is low and needs adjusting. There is a danger of losing communications with the antenna or having command parity errors. |
|
| 321 | L3 1200 MHZ VCO OUTPUT LOW, > -0.8 VSee example overlay | The 1200 MHZ VCO output power is low. The L3 will need to be replaced. The problem is not critical unless other errors occur at the same time. |
|
| 322 | L3 1800 VCO OUTPUT LOW, > -0.8 VSee example overlay | The 1800 MHZ VCO output power is low. The L3 will need to be replaced. The problem is not critical unless other errors occur at the same time. |
|
| 323 | L1 VCXO TUNING > 2 VSee example overlay | The VCXO tuning voltage in the L1 has drifted out of range and needs to be adjusted. The problem is not critical unless other errors occur at the same time. |
|
| 324 | L5 5 MHZ PHASE > -0.3 VSee example overlay | The 5 MHZ phase monitored in the L5 has drifted to near the boundary and there is a danger of a cycle slip. The phase needs to be zeroed. |
|
| 325 | 5 MHZ PHASE JUMP; CYCLE SLIPSee example overlay | A 5 MHZ phase jump/cycle slip has occurred. Some data will be lost. |
|
| 340 | T2 GROUND > 0.15 VSee example overlay | This message is generated when there is a loose ground connection or a problem in the data set. | Do nothing. The LO/IF group routinely monitors this, and will correct the problem. |
| 342 | RACK B TEMP NOT 16 TO 23 CSee example overlay | The temperature of the B-rack is out of range. |
|
| 350 | ANTENNA T1 PLL INTEGRATOR > 5VSee example overlay | The Integrator circuit in the T1 has drifted out of range, and could go out of lock. The problem is not critical unless there are problems communicating with the antenna. |
|
| 355 | ANTENNA T1 MANUAL WARNINGSee example overlay | The T1 manual warning flag has been set. |
|
| 357 | ANTENNA T1 NOT LOCKED-PLEASE RESETSee example overlay | The T1 has either lost lock or glitched lock. |
|
| 402 | RACK B +5 V: ERROR > 0.1 VSee example overlay | The +5 volts in the antenna has drifted out of the range 5.0 V to 5.2 V. |
|
| 403 | RACK B -5 V: ERROR > 0.1 VSee example overlay | The -5 volts in the antenna has drifted out of the range -5.1 V to -5.3V. |
|
| 404 | L6(A) +15 V: ERROR > 0.2 VSee example overlay | The +15 volts in the antenna has drifted out of the range . |
|
| 405 | L6(A) -15 V: ERROR > 0.2 VSee example overlay | The -15 volts in the antenna has drifted out of range. |
|
| 407 | L6(A) -28 V: ERROR > 0.4 VSee example overlay | The -28 volts in the antenna has drifted out of range. |
|
| 447 | L6(C) +28 V: ERROR < 27.4 V OR > 28.6 VSee example overlay | The +28 volts in the antenna has drifted out of range. |
|
| 506 | L2 50 MHZ PLL NOT LOCKEDSee example overlay | The 50 MHZ VCO in the L2 has lost lock. |
|
| 511 | L3 1200 MHZ PLL NOT LOCKEDSee example overlay | The 1200 MHZ VCO in the L3 has lost lock. |
|
| 520 | L3 1800 MHZ PLL NOT LOCKEDSee example overlay | The 1800 MHZ VCO in the L3 has lost lock. |
|
| 523 | L1 VCXO TUNING OUT OF RANGESee example overlay | The VCXO tuning voltage in the L1 has drifted out of range and needs to be adjusted. |
|
| 526 | 5 MHZ LOCK SELECTEDSee example overlay | The 5 MHZ lock has been selected. This will occur when there is a problem with the 600 MHZ phase. Data will be lost. |
|
| 527 | ANTENNA LO ABNORMAL STATE SELECTEDSee example overlay | This abnormal state occurs when the antenna has been commanded to lock on the 5 MHZ. The LO system in the antenna needs to be reset. |
|
| 542 | RACK B TEMP JUMP >2CSee example overlay | There has been a temperature jump in the B-rack of the antenna. |
|
| 545 | ANTENNA T2 XMT LEVEL OUT OF RANGESee example overlay | The T2 transmit level in the antenna is out of range. The T2 probably needs to be replaced and recalibrated. | Do nothing. The LO/IF group routinely monitors this, and will correct the problem. |
| 546 | ANTENNA T2 RCV LEVEL OUT OF RANGESee example overlay | The T2 receive level at the antenna is out of range. The antenna needs the levels reset. |
|
| 601 | CLIPPER LEVEL OUT OF RANGE See example overlay | The power level of the IF going in to the sampler module could be too high or too low. This message could also be caused by sampler threshold voltages that are incorrect. |
|
| 602 | SINE X COSINE TOO LARGE (sampler related)See example overlay | If in continuum mode, the sampler is misadjusted. If in spectral line mode, ignore. |
|
| 700 | L8 OUT OF SYNC. See example overlay | L8 is out of synchronization. |
|
| 701 | SYNTHESIZER AT WRONG FREQUENCYSee example overlay | When observe file & L6 disagree - probably a lost command; maybe broken L6 or DCS. |
|
| 702 | SYNTHESIZER OUT OF LOCKSee example overlay | One of the L6s is out of lock. |
|
| 703 | LOSS OF AIRFLOW IN VERTEX ROOM | (not currently in use) | N/A |
| 750 | IF FILTER(S) MIS-SELECTEDSee example overlay | Backend filters in the T4 are not selected properly. |
|
|
|
|
|
|
| 825 | A TSYS > 4 TIMES NOMINALSee example overlay | The synchronous detector voltage is too low. Indicates loss of sensitivity, loss of bright sky or bad noise calibration. |
|
| 826 | A TOT PWR OUT OF RANGE 2.9 TO 3.1See example overlay | The receiver gain has changed more than the F4 Automatic Level Control can handle, allowing the Total Power Detector output to vary from its controlled level of 3.0 V. If the ALC is also less than 0.5 V, the IF is bad. If the ALC is ok, data from this IF may be bad. |
|
| 828 | A ALC < 0.5 VSee example overlay | The F4 Automatic Level Control is at the limit of its control voltage and is no longer effective. |
|
| 830 | B TSYS > 4 TIMES NOMINALSee example overlay | The synchronous detector voltage is too low. Indicates loss of sensitivity, loss of bright sky or bad noise calibration. |
|
| 835 | B ALC < 0.5VSee example overlay | The F4 Automatic Level Control is at the limit of its control voltage and is no longer effective. |
|
| 836 | B TOT PWR OUT OF RANGE 2.9 TO 3.1See example overlay | The receiver gain has changed more than the F4 Automatic Level Control can handle, allowing the Total Power Detector output to vary from its controlled level of 3.0 V. |
|
| 845 | C TSYS > 4 TIMES NOMINALSee example overlay | The synchronous detector voltage is too low. Indicates loss of sensitivity, loss of bright sky or bad noise calibration. |
|
| 846 | C TOT PWR OUT OF RANGE 2.9 TO 3.1See example overlay | The receiver gain has changed more than the F4 Automatic Level Control can handle, allowing the Total Power Detector output to vary from its controlled level of 3.0 V. |
|
| 848 | C ALC < 0.5VSee example overlay | The F4 Automatic Level Control is at the limit of its control voltage and is no longer effective. |
|
| 850 | D TSYS > 4 TIMES NOMINALSee example overlay | The synchronous detector voltage is too low. Indicates loss of sensitivity, loss of bright sky or bad noise calibration. |
|
| 855 | D ALC < 0.5VSee example overlay | The F4 Automatic Level Control is at the limit of its control voltage and is no longer effective. |
|
| 856 | D TOT PWR OUT OF RANGE 2.9 TO 3.1See example overlay | The receiver gain has changed more than the F4 Automatic Level Control can handle, allowing the Total Power Detector output to vary from its controlled level of 3.0 V. |
|
| 867 | RACK A -15V: ERROR > 2%See example overlay | The -15V supply voltage for the A-Rack is out of tolerance. This problem does not affect data unless other checker messages indicate a loss of data. |
|
| 868 | RACK A +5V: ERROR > 2%See example overlay | The +5V supply voltage for the A-Rack is out of tolerance. This problem does not affect data unless other checker messages indicate a loss of data. |
|
| 869 | RACK A +15V:ERROR > 2%See example overlay | The +15V supply voltage for the A-Rack is out of tolerance. This problem does not affect data unless other checker messages indicate a loss of data. |
|
| 878 | F5 10 VOLT ERROR > 0.035 VSee example overlay | The 10 V precision reference in the F5 module is in error, or the readback of the 10 V precision reference is bad. If the readback is bad, it may be caused by a bad analog multiplexer in the F5 or a bad A/D converter in the data set. If the 10 V precision reference is correct, but the readbacks are bad, all of the A/D conversions involving the F5 may be in error. |
|
| 879 | F5 GROUND: ERROR >0.015 VSee example overlay | The ground reference in the F5 module is in error, or the readback of the ground reference is bad. If the readback is bad, it may be caused by a bad analog multiplexer in the F5 or a bad A/D converter in the data set. If the ground reference is correct, but the readbacks are bad, all of the A/D conversions involving the F5 may be in error. |
|
| 905 | F5 TEMPERATURE NOT 20 TO 30 CSee example overlay | The temperature monitor in the F5 is out of range, indicating a problem with the cooling/heating air supply to the A-Rack. A calibration problem with the temperature sensor can also cause this error, even when the temperature is within range. |
|
| 914 | F2 PLL NOT LOCKED AND OBSERVING AT L BANDSee example overlay | The F2 is the first LO for L-band (1.5 GHz). The antenna will not fringe at L-band if it is not phase-locked. |
|
|
|
|
|
|
| 940 | L9 1200 MHZ RCV LEVEL < 0.6See example overlay | The central 1200 MHZ receive level in the L9 is low. |
|
| 941 | L9 1800 MHZ RCV LEVEL < 0.6See example overlay | The central 1800 MHZ receive level in the L9 is low. If this level goes too low then the antenna data sets will be missing or there will be high monitor parity errors. |
|
| 942 | L14 1200 MHZ VCO OUTPUT LOW,>-0.6See example overlay | The 1200 VCO output power is low. The L14 will need to be replaced. |
|
| 943 | L14 1800 MHZ VCO OUTPUT LOW, >-0.6See example overlay | The 1800 VCO output power is low. The L14 will need to be replaced. |
|
| 944 | L14 1200 MHZ PLL NOT LOCKEDSee example overlay | The 1200 MHZ VCO in the L14 has lost lock. The L14 needs to be replaced. |
|
| 945 | L14 1200 MHZ PLL TUNING NOT -5 TO +8See example overlay | The tuning voltage of the 1200 VCO in the L3 has drifted out of range. The VCO should still be locked and ok but will need adjusting. |
|
| 946 | L14 1800 MHZ PLL NOT LOCKEDSee example overlay | The 1800 MHZ VCO in the L14 has lost lock. The L14 needs to be replaced. |
|
| 947 | L14 1800 MHZ PLL TUNING NOT -5 TO +8See example overlay | The tuning voltage of the 1800 VCO in the L14 has drifted out of range. The VCO should still be locked and ok but will need adjusting. |
|
| 948 | L11 +15V. ERROR > 0.2See example overlay | The +15 volts in the D-rack has drifted out of range. The voltage is not stable or near the limits. |
|
| 949 | L11 GROUND > 0.015See example overlay | This message is generated when there is a loose ground connection or a problem in the data set. |
|
| 950 | L11 -15V. ERROR > 0.2See example overlay | The -15 volts in the D-rack has drifted out of range. The voltage is not stable or near the limits. |
|
| 951 | CENTRAL T2 GROUND >0.015See example overlay | This message is generated when there is a loose ground connection or a problem in the data set. | Do nothing. The LO/IF group routinely monitors this, and will correct the problem. |
| 952 | CENTRAL T2 XMIT LEVEL OUT OF RANGESee example overlay | The T2 transmit level in the D-rack is out of range. The T2 probably needs to be replaced and recalibrated. |
|
| 953 | CENTRAL T2 RCV LEVEL OUT OF RANGESee example overlay | The T2 receive level in the D-rack is out of range. The T2 may need to be replaced and recalibrated. It is also possible that the IF signals are weak or not present.This error can also be caused by interference (RFI). It is also possible that the front end is not set up properly. |
|
| 954 | CENTRAL T1 IN MANUALSee example overlay | The T1 manual warning flag has been set. |
|
| 955 | CENTRAL T1 PLL NOT LOCKEDSee example overlay | The T1 has either lost lock or glitched lock. Try resetting the T1. If the T1 will not reset or if it continues to glitch lock. |
|
| 956 | CENTRAL T1 PLL INTEGRATOR >5V.See example overlay | The Integrator circuit in the T1 has drifted out of range. The T1 needs to be replaced. |
|
| 957 | T5-A ALC OUT OF RANGESee example overlay | The T5 automatic level control voltage (ALC) is out of range. It should be in the range of -2.5 V to -6.0 V. This could be caused by problems with the T5, T4, or sampler. It could also happen because the IF entering the T5 has a power level that is too low. |
|
| 958 | T5-C ALC OUT OF RANGESee example overlay | The T5 automatic level control voltage (ALC) is out of range. It should be in the range of -2.5 V to -6.0 V. This could be caused by problems with the T5, T4, or sampler. It could also happen because the IF entering the T5 has a power level that is too low. |
|
| 959 | T5-A IF LEVEL OUT OF RANGESee example overlay | Total power as monitored in the T5 is out of range. There could be a problem with the automatic level control circuit in the T5 or sampler. If the total power is too high, then the T5 is either oscillating or not automatic level controlling. If the total power is too low, there may not be sufficient power in the IF as it enters the T5, or there could be a problem with the fluke relays. |
|
| 960 | T5-C IF LEVEL OUT OF RANGESee example overlay | Total power as monitored in the T5 is out of range. There could be a problem with the automatic level control circuit in the T5 or sampler. If the total power is too high, then the T5 is either oscillating or not automatic level controlling. If the total power is too low, there may not be sufficient power in the IF as it enters the T5, or there could be a problem with the fluke relays. |
|
| 961 | T6 +5V. ERROR > 0.1See example overlay | The +5 volts in the D-rack is out of range. |
|
| 962 | T6 -5V. ERROR >0.1See example overlay | The -5 volts in the D-rack is out of range. |
|
| 963 | T6 +28V. ERROR > 0.4See example overlay | The +28 volts in the D-rack is out of range. |
|
| 964 | T6 -28V. ERROR > 0.4See example overlay | The -28 volts in the D-rack is out of range. |
|
|
965 |
L11 VCO OUT OF RANGESee example overlay | The VCO in the L11 is out of range. The L11 will need to be replaced for adjustment. |
|
| 966 | T5-B ALC OUT OF RANGESee example overlay | The T5 automatic level control voltage (ALC) is out of range. It should be in the range of -2.5 V to -6.0 V. This could be caused by problems with the T5, T4, or sampler. It could also happen because the IF entering the T5 has a power level that is too low. |
|
| 967 | T5-D ALC OUT OF RANGESee example overlay | The T5 automatic level control voltage (ALC) is out of range. It should be in the range of -2.5 V to -6.0 V. This could be caused by problems with the T5, T4, or sampler. It could also happen because the IF entering the T5 has a power level that is too low. |
|
| 968 | T5-B IF LEVEL OUT OF RANGESee example overlay | Total power as monitored in the T5 is out of range. There could be a problem with the automatic level control circuit in the T5 or sampler. If the total power is too high, then the T5 is either oscillating or not automatic level controlling. If the total power is too low, there may not be sufficient power in the IF as it enters the T5, or there could be a problem with the fluke relays. |
|
| 969 | T5-D IF LEVEL OUT OF RANGESee example overlay | Total power as monitored in the T5 is out of range. There could be a problem with the automatic level control circuit in the T5 or sampler. If the total power is too high, then the T5 is either oscillating or not automatic level controlling. If the total power is too low, there may not be sufficient power in the IF as it enters the T5, or there could be a problem with the fluke relays. |
|
|
|
|
|
|
| 970 | K/U/Q LO OUT OF LOCKSee example overlay | The F3 is the first LO for K and U and Q bands (23, 15, and 43, GHz). The antenna will not fringe at these bands if it is not phase-locked |
|
| 971 | F12 IN MANUALSee example overlay | The F12, the first LO for X-band (8.4 GHz) and the second LO for Q band, has been left switched to "Local" and cannot be controlled remotely. |
|
| 972 | F12 NOT LOCKEDSee example overlay | The F12 is the first LO for X-band (8.4 GHz) and the second LO for Q- band . The antenna will not fringe at these bands if it is not phase-locked. |
|
| 980 | EXCESSIVE A RACK DEWAR TEMPERATURE See example overlay | The Dewar for the C, U, and old-style K band (4.8, 15, and 23 GHz) amplifiers is warmer than 30 K. This will increase Tsys. If the temperature is above 100K, then all data is bad. |
|
| 981 | VLA DEWAR PRESSURE >7 MICRONSSee example overlay | There is air in the A rack dewar. It may be leaking, or it may not have been completely evacuated. |
|
| 982 | CHECK HELIUM PRESSURESee example overlay | The supply pressure should be 200 to 300 psi. The nominal return pressure is 50-75 psi. The typical failure is when the Supply and Return pressures aproach each other until they are they same. |
|
| 983 | 8GHZ DEWAR WARMSee example overlay | The Dewar for X-band (8.4 GHz) is warmer than its nominal operating temperature. This will increase Tsys. If the temperature is above 100K, then all data is bad. |
|
| 984 | L-BAND DEWAR WARMSee example overlay | The Dewar for L-band (1.5 GHz) is warmer than its nominal operating temperature. This will increase Tsys. If the temperature is above 100K, then all data is bad. |
|
| 985 | Q-BAND DEWAR WARMSee example overlay | The Dewar for Q-band (45 GHz) is warmer than its nominal operating temperature. This will increase Tsys. If the temperature is above 100K, then all data is bad. |
|
| 986 | K-BAND DEWAR WARMSee example overlay | The Dewar for K-band (23 GHz) is warmer than its nominal operating temperature. This will increase Tsys. If the temperature is above 100K, then all data is bad. |
|
|
|
|
|
|
| 1000 | CHECK REFERENCE PHASE IN 'POINTING' FILESee example overlay | The 600 MHZ phase has drifted out of the window previously specified. A new reference phase needs to be set. |
|
| 1001 | 600 MHZ RT PHASE JUMP See example overlay | A jump in round trip phase has occurred. |
|
With one exception message numbers 1100 and above
are reserved for
reporting problems deduced from data from antenna
"0".
|
|
|
|
|
| 1100 | WEATHER STATION MALFUNCTION | Caused by one or more of the following conditions:
1) Wind Speed < 0 V. 2) Barometer & Temp < 0 V. 3) Dewpoint > 4.5 V. (~40 C) |
|
| 1101 | WIND NEAR ANTENNA STOW LIMIT (wind at *CB* > 18m/s)See example overlay | High wind detected. |
|
| 1102 | WIND AT ANTENNA NEAR STOW LIMIT (wind at *antenna* >40mph) | High wind detected. |
|
| 1103 | CHECK FEED DE-ICER STATE | Dewpoint/Temperature indicate possible icing on array. |
|
| 1104 | NO ** SOCORRO POWER | Socorro Electric dropped power, generators came up-you know that or you wouldn't be reading screen. Alarm is also used to stagger slewing to ease inductive load on generators. | ? |
| 1105 | DP > TEMPERATURE! | TSL failure. |
|
| 1200 | L16 ERRORSee example overlay | The L16 has incurred an error. The error could be loss of 5 MHZ or low power. |
|
| 1201 | VERIFY FLUKE SETTINGS (A/C)(RACK-1)See example overlay | The message occurs when the L17 is out of lock. The L17 will not lock unless the Flukes are set up as follows FLUKE A +2x(FLUKE C) = 350 MHZ. |
|
| 1202 | VERIFY FLUKE SETTINGS (B/D)(RACK-1)See example overlay | The message occurs when the L17 is out of lock. The L17 will not lock unless the Flukes are set up as follows FLUKE D +2x(FLUKE B) = 350 MHZ. |
|
| 1203 | VERIFY FLUKE SETTINGS (B/D)(RACK-2)See example overlay | The message occurs when the L17 is out of lock. The L17 will not lock unless the Flukes are set up as follows FLUKE D +2x(FLUKE B) = 350 MHZ. |
|
| 1204 | VERIFY FLUKE SETTINGS (A/C)(RACK-2)See example overlay | The message occurs when the L17 is out of lock. The L17 will not lock unless the Flukes are set up as follows FLUKE A +2x(FLUKE C) = 350 MHZ. |
|
| 1205 | L12 OUT OF LOCK See example overlay |
This indicates when the 19.2 Hz is out of lock. |
|
| 1206 | WEST ARM WG PRESSURE PROBLEM See example overlay |
The nominal pressure of nitrogen in the waveguide is 4 lbs. A drop in pressure indicates a leak |
|
| 1207 | NORTH ARM WG PRESSURE PROBLEM See example overlay |
The nominal pressure of nitrogen in the waveguide is 4 lbs. A drop in pressure indicates a leak |
|
| 1208 | EAST ARM WG PRESSURE PROBLEM See example overlay |
The nominal pressure of nitrogen in the waveguide is 4 lbs. A drop in pressure indicates a leak |
|